The CTL-SEN-Mini/9508 Series is a compact, high-precision motion sensor powered by advanced 5.8G High-Bay radar technology. Designed for discreet architectural integration, it features a miniature form factor (Φ35 mm cutout) while delivering robust detection coverage capable of accurately distinguishing between major and minor motion. This series supports convenient parameter configuration via an IR remote control and offers a wide range of mounting accessories to ensure seamless installation across diverse application scenarios.
Features
Accurately identifies major motion and minor motion.
Sensitivity and detection range can be adjusted independently.
Supports multiple protocols via RS485, including Modbus-RTU and Active Reporting.
Supports parameter configuration and status readout via IR remote control.
Indicator LED indicator defaults to OFF; configurable to Breathing or Night Light modes.
Powered by a proprietary module with advanced signal processing algorithms.
Achieves a micro-motion detection diameter of at least 10.0 m at 3.0 m height
Detection Range
1.5 to 18.0 m (sensor to target)
Sensitivity
0 to 100%
Delay Time
1 to 3,600 seconds
Product Size
Φ43 mm x 25 mm
Cutout Size
Φ35 mm
Product Weight
16.5 g
Cable Assembly
UL1007 22AWG Cable Length: 150 mm
Operating Temperature
Indoor -20 to 45°C
Operating Humidity
< 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Front View
Top View
Dimensions
Measuring 43 mm in diameter and 25 mm in depth, this recessed unit fits a 35 mm cutout. Optional kits allow for surface, wall, or universal bracket mounting.
Product Dimensions
Applications
Hotel
Mounting
Interference Avoidance: Avoid installing near constantly moving objects (e.g., curtains, plants) or large reflective surfaces (e.g., metal ducts, mirrors) to minimize false alarms or unintended triggering.
Device Spacing: Maintain a minimum distance of 4 m between multiple sensors to prevent mutual interference.
Mounting: Ensure the installation surface is vibration-free. Note that radar signals can penetrate non-metallic surfaces; avoid moving objects directly behind the installation wall/ceiling.
Wiring Safety: Disconnect power before wiring. Use certified cables and ensure the circuit includes appropriate short-circuit and overload protection.
Disclaimer: Product specifications are subject to change without prior notice for improvement purposes. Please follow all wiring diagrams strictly. The manufacturer is not liable for issues caused by improper installation.
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
FAQ
What is the core advantage of this RS485 model in the hotel guest control system?
Adopts stable and reliable industrial-grade RS485 bus communication, supporting Modbus-RTU protocol and active reporting. This allows it to transmit high-precision 5.8G micro-motion detection data wired to the guest room RCU host with zero delay, possessing strong anti-external electromagnetic interference capabilities.
What is the power supply voltage specification of the device?
Designed for centralized low-voltage power supply, the input voltage supports a wide range of DC 12 ~ 30 V. The maximum operating power consumption is only 0.5W, typically powered directly by the RCU mainboard, making wiring simple.
With no physical dip dial on-site, how to set the RS485 address?
Because the probe body pursues extreme miniaturization (outer diameter only 43mm), mechanical dip dials are eliminated. Electricians need to assign addresses from 01~99 by writing to registers using commands via the RS485 host backend or with the help of a dedicated serial configuration tool.
Will the 5.8G radar sense people in the corridor through the wall?
Highly likely. The 5.8GHz frequency band has strong non-metallic penetrability and can easily penetrate thin wooden doors or plaster partition walls. When installed at the edge of a hotel room, the RC1 remote controller must be used to lower the radar's sensitivity and shrink the detection radius to prevent cross-zone false alarms.
What are the anti-crosstalk requirements when daisy-chaining multiple RS485 radar devices?
It is recommended to use standard twisted shielded pair cables for communication wires; a 120-ohm terminating resistor should be paralleled at the end of the bus. To prevent microwave signal mutual interference, two 5.8G radars should try to maintain a straight-line spacing of over 4 meters.
What are the body dimensions and concealed installation depth requirements?
The body is extremely compact, outer diameter 43 mm, height only 25 mm. The ceiling cutout requires 35 mm, and it only needs to provide a shallow gap slightly larger than 25mm inside to smoothly embed, making it very suitable for ultra-thin suspended ceilings.
Is it feasible to install in the restroom shower area?
Needs careful consideration. The device's housing protection rating is IP20, without waterproof functions. Water vapor condensation clinging to the sensing surface may not only corrode the motherboard but also severely attenuate radar microwave signals. Recommended to install in the dry zone of wet/dry separated areas.
If the RCU host is not yet connected, can the probe's condition be verified on-site?
Supported. The probe contains a micro LED status indicator. On-site personnel can use the RC1 remote controller to issue test commands to it. By observing the indicator's feedback when there is human activity, the normal operation of the underlying perception hardware can be confirmed.