The CTL-SEN-Mini/9211.F21 is a compact, high-precision presence sensor powered by advanced 24GHz FMCW mmWave technology. Designed for discreet, premium applications, it features a miniature form factor (Φ35 mm cutout) and offers a detection diameter of up to 8.0 m.
Features
Accurately identifies motion, micro-motion, and Presence.
Sensitivity and detection distance can be adjusted independently.
Features 1 relay output
Supports parameter configuration and status readout via IR remote control.
Indicator LED indicator defaults to OFF; configurable to Breathing or Night Light modes.
Powered by a proprietary module with advanced signal processing algorithms.
Specifications
Output Type
Mains Output
BOX Input Voltage
AC 100 to 240 V
BOX Output Voltage
DC 12 V (< 500 mA)
Sensor Input Voltage
DC 12 V
Power Consumption
0.5 W (Max)
Relay Output
Normally Open Mode Normally Closed Mode
Relay Load
AC 100 to 240 V, ≤ 5 A
Indicator Light
LED
Detection Mode
24GHz FMCW Radar
Operating Frequency
24.00 to 24.25 GHz
Transmit Power
≤ 10 dBm
Installation Method
Recessed Ceiling Mount
Mounting Height
2.0 to 4.0 m
Detection Angle
360°
Detection Coverage
Installation at 3.0 m Height: ① Motion & Micro-motion: Detection diameter at least 8.0 m ② Stationary Presence: Detection diameter at least 6.0 m
Detection Range
1.5 to 8.0 m (sensor to target)
Sensitivity
0 to 100%
Delay Time
1 to 3,600 seconds
Product Size
Φ43 mm x 25 mm
Cutout Size
Φ35 mm
Product Weight
17.5 g
BOX Size
121 mm x 35 mm x 26 mm
BOX Weight
88 g
Cable Assembly
UL2468 22AWG Cable Length: 200 mm
Operating Temperature
Indoor -20 to 45°C
Operating Humidity
< 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Front View
Side View
Dimensions
Measuring 43 mm wide and 25 mm deep, this recessed unit fits a 35 mm cutout and requires a minimum ceiling depth of 13 cm.
Product Dimensions
Applications
Hotel
Mounting
Interference Avoidance: Keep away from moving objects (e.g., curtains, plants) and large metal/reflective surfaces.
Device Spacing: Maintain at least 4m between sensors.
Mounting: Install on a stable, vibration-free surface. Ensure no moving objects are behind the wall (signals penetrate non-metals).
Wiring Safety: Turn off power before wiring. Use certified cables and proper circuit protection.
Disclaimer: Follow wiring diagrams strictly. Manufacturer is not liable for improper installation. Specifications subject to change.
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
FAQ
What is the core difference between the S1-Plus version and the S2 version?
The S1-Plus is also purely local hardwired control with a matching strip-shaped control box. However, it integrates only 1 ultra-high power relay internally, with a single-channel maximum control current up to 5A, suitable for series-controlling high-load main lighting strips or equipment with a total power of about 1KW.
How large is the coverage range of the 24GHz FMCW radar?
When installed vertically at a 3.0-meter height, the dynamic walking detection diameter can reach 8.0 meters, and the detection diameter for capturing micro-motions and static breathing is about 6.0 meters, offering broad and detailed coverage.
If the installation position is too close to the guest room corridor, will it sense pedestrians in the corridor?
Highly likely. Due to the strong penetrability of millimeter waves, radar waves may pass through thin walls or wooden doors. During installation and debugging, electricians must use the remote control to lower the radar detection sensitivity or shrink the detection distance threshold to prevent cross-boundary detection.
How to wire if there is a need for forced continuous lighting on-site?
The control box reserves external manual override switch terminals. After connecting a normal wall switch, operating the switch can bypass the radar detection logic, forcibly keeping the internal relay closed to achieve constant lighting.
What are the cutout size and hiding depth requirements for the sensor body?
The probe requires a 35 mm cutout and an outer diameter of 43 mm; because the matching control box is long (length up to 121mm), it is recommended to reserve a vertical clearance depth of over 13 cm inside the ceiling for wiring and placing the equipment.
Can the LED indicator inside the body be turned off?
To not affect guests' rest, the LED indicator is turned off by default at the factory. If there are specific needs, it can be configured as a breathing light or night light mode via the remote controller.
Does it have illuminance detection to achieve energy saving?
Yes, the probe integrates a 0-32,000 Lux high-precision ambient light sensor internally. When the guest room has good daylighting during the day, the radar will not close the high-voltage relay to turn on lights even if it detects a person.
If a remote controller is not configured on-site, can the radar work?
Yes. The device comes with a balanced set of default parameters from the factory (such as default delay time, moderate sensitivity). After power-on, it can perform human presence detection and hardwired light control normally.