The CTL-SEN-R5/2308 is a high-precision 24GHz millimeter-wave radar sensor designed for advanced occupancy detection. It features an adjustable range of 1.5 to 7m with centimeter-level accuracy and a flexible 0° to 60° tilt design for versatile installation. Beyond detecting movement, its "micro-motion" technology can identify static presence (like breathing), while customizable sensing zones and an integrated ambient light sensor enable intelligent automation for smart homes, offices, and healthcare, ensuring efficient energy management based on real-time human displacement.
Features
Supports motion, micro-motion, and stationary presence detection.
Features customizable multi-zone sensing (Segments A/B/C) and configurable proximity/recession distance thresholds.
Integrated high-precision sensor for accurate indoor illuminance monitoring.
Supports multiple protocols via RS485, including Modbus-RTU and Active Reporting.
Sensitivity and detection range can be configured independently.
Features a 0 to 60° adjustable detection angle for precise zone targeting.
Supports parameter configuration and query via IR remote control.
Indicator LED brightness automatically adjusts to ambient light levels.
Specifications
Communication Type
RS485 + Dry Contact
Input Voltage
DC 12 to 30 V
Power Consumption
0.5 W (Max)
Serial Port Settings
Baud Rate: 1200 to 115200 Data Bits: 8 Parity: None, Even, Odd Stop Bits: 1 to 2 Default: 9600, 8, None, 1
Address Range
01 to 69 (Decimal)
Dry Contact Output
Normally Open Mode, Normally Closed Mode, Normally Open Pulse, Normally Closed Pulse
Dry Contact Load
AC or DC ≤ 30 V, ≤ 200mA
Indicator Light
LED
Detection Mode
24GHz FMCW Radar
Operating Frequency
24.00 to 24.25 GHz
Transmit Power
≤ 10 dBm
Installation Method
Recessed Ceiling Mount
Mounting Height
2.0 to 4.0 m
Detection Angle
360°
Detection Coverage
Mounting Height: 3 m At 0°: Φ 1.5 m detection range At 60°: 3.0 x 7.0 m detection range
Detection Range
1.5 to 7.0 m (sensor to target)
Illuminance Monitoring
0 to 32,000 Lux (Accuracy ±4%)
Delay Time
1 to 3,600 seconds
Product Size
Φ65 mm x 60 mm
Cutout Size
Φ55 mm
Product Weight
62 g
Cable Assembly
UL1007 20AWG Cable Length: 150 mm
Operating Temperature
Indoor -20 to 45°C
Operating Humidity
< 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Supporting flexible installation angle adjustments, this radar ranging sensor provides distinct coverage patterns at a standard mounting height of 3.0 meters:
0° vertical mounting: Delivers a circularly symmetrical coverage with a horizontal detection diameter of approximately 1.5 meters.
60° angled mounting: Delivers a directional fan-shaped/elliptical coverage, achieving a maximum forward detection span of up to 6.8 meters, a backward detection range of approximately 0.2 meters, a maximum overall transverse width of approximately 7.0 meters, and a longitudinal span of approximately 3.0 meters.
0° Front View
0° Front View
0° Top View
0° Top View
60° Front View
60° Front View
Dimensions
Product Dimensions
Applications
HomeHotelLightingOfficeSecurity
Mounting
Interference Avoidance: Avoid installing near constantly moving objects (e.g., curtains, plants) or large reflective surfaces (e.g., metal ducts, mirrors) to prevent false triggering.
Device Spacing: Maintain a minimum distance of 4 meters between multiple sensors to prevent mutual interference.
Mounting: Ensure the installation surface is vibration-free. Note that radar signals can penetrate surfaces; avoid moving objects directly behind the installation wall/ceiling.
Wiring Safety: Disconnect power before wiring. Use certified cables and ensure the circuit includes appropriate short-circuit and overload protection.
Disclaimer: Specifications are subject to change without notice. Please follow all wiring diagrams strictly. The manufacturer is not liable for issues caused by improper installation.
Wiring Diagram
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
Control4 - Composer Pro
Control4 Composer Pro is a professional-grade integration software for luxury whole-home audio/video and automation systems, exclusively available to certified dealers to seamlessly integrate entertainment hubs, complex subsystems, and custom smart scenes.
FAQ
What low-voltage interfaces does this R5-Rang-485 model support?
This is a pure low-voltage model. The rear cable provides an RS485 bus interface (running Modbus-RTU protocol) and simultaneously provides 1-channel dry contact signal output (supporting normally open, normally closed, and pulse modes), suitable for connection to security hosts or building systems.
Compared to other presence sensors, what is the core advantage of R5-Rang in detection capability?
Features centimeter-level high-precision distance measurement capability. It not only identifies static breathing through "micro-motion" technology but also tracks the exact displacement of the target in real-time, achieving automation control based on precise distance segments.
How does the 0-60° angle adjustment change the ranging detection range?
At a 3-meter mounting height: if the sensing surface is 0° vertically downwards, its ground detection circle diameter is 1.5 meters (highly focused); if the sensing surface is tilted to the maximum 60°, the ranging coverage changes to an oval area of 7.0m long x 3.0m wide, covering farther targets.
How to quickly set the RS485 address on-site without a computer?
There are two "decimal rotary dials" on the back of the body. Electricians can directly use a screwdriver to dial them to the required slave address (01-99) on-site, eliminating tedious software flashing steps.
Can the internal dry contact directly control 220V luminaires or fans?
Absolutely not. The dry contact can only withstand a maximum low-voltage signal of 30V/200mA. To control 220V high-voltage loads, a high-power AC contactor or solid-state relay must be externally attached behind the dry contact.
What are the body dimensions and ceiling installation depth requirements?
The body outer diameter is 65 mm, and the height reaches 60 mm. It requires a ceiling cutout diameter of 55 mm, and the vertical clearance depth inside the ceiling must be greater than 65 mm to insert the body.
Will large exhaust fans rotating in the installation environment affect detection?
It will have a severe impact. The regular rotation of exhaust fan blades will be misjudged by the Doppler radar as continuous personnel walking. You must use the adjustable angle function to tilt the radar sensing surface away from the fan area, or relocate the installation entirely.
Before the bus system is debugged, does it support local infrared single-unit verification?
Yes. You can use the RC1 infrared remote controller aimed directly at the multi-function window of the sensing surface to issue local non-contact commands like light threshold and delay (1-3600s) for independent verification.