The CTL-SEN-R5/2303 is a high-precision 24GHz millimeter-wave radar sensor designed for advanced occupancy detection. It features an adjustable range of 1.5 to 7m with centimeter-level accuracy and a flexible 0° to 60° tilt design for versatile installation. Beyond detecting movement, its "micro-motion" technology can identify static presence (like breathing), while customizable sensing zones and an integrated ambient light sensor enable intelligent automation for smart homes, offices, and healthcare, ensuring efficient energy management based on real-time human displacement.
Features
Features customizable multi-zone sensing (Segments A/B/C) and configurable proximity/recession distance thresholds.
Integrated high-precision sensor for accurate indoor illuminance monitoring.
Supports 4 independent channels for lighting control.
Supports multiple operating modes, including Fully Automatic, Semi-Automatic, Master/Slave, and Day/Night.
Supports parameter configuration and status readout via IR remote control.
Built-in logic functions with support for manual mode and independent event outputs.
Supports external inputs to dynamically modify parameter characteristics.
Offers selectable Easy (quick start) and Advanced (multi-channel output) modes.
Specifications
Communication Type
KNX TP
Input Voltage
DC 21 to 30 V
Operating Current
≤ 6 mA
Auxiliary Voltage
DC 12 to 30 V (< 3 W)
Indicator Light
RGB LED
Detection Mode
24GHz FMCW Radar
Operating Frequency
24.00 to 24.25 GHz
Transmit Power
≤ 10 dBm
Installation Method
Recessed Ceiling Mount
Mounting Height
2.0 to 4.0 m
Detection Angle
360°
Detection Coverage
Mounting Height: 3 m At 0°: Φ 1.5 m detection range At 60°: 3.0 x 7.0 m detection range
Detection Range
1.5 to 7.0 m (sensor to target)
Illuminance Monitoring
0 to 32,000 Lux (Accuracy ±4%)
Delay Time
1 to 3,600 seconds
Product Size
Φ65 mm x 60 mm
Cutout Size
Φ55 mm
Product Weight
67.5 g
Bus Terminal
Red / Black
Power Terminal
Yellow / white
Programming button
Physical Address Assignment
Bus Connection
Φ0.6 to 0.8 mm
Operating Temperature
Indoor -20 to 45°C
Operating Humidity
< 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Supporting flexible installation angle adjustments, this radar ranging sensor provides distinct coverage patterns at a standard mounting height of 3.0 meters:
0° vertical mounting: Delivers a circularly symmetrical coverage with a horizontal detection diameter of approximately 1.5 meters.
60° angled mounting: Delivers a directional fan-shaped/elliptical coverage, achieving a maximum forward detection span of up to 6.8 meters, a backward detection range of approximately 0.2 meters, a maximum overall transverse width of approximately 7.0 meters, and a longitudinal span of approximately 3.0 meters.
0° Front View
0° Front View
0° Top View
0° Top View
60° Front View
60° Front View
Dimensions
Product Dimensions
Applications
HomeHotelLightingOfficeSecurity
Mounting
Interference Avoidance: Avoid installing near constantly moving objects (e.g., curtains, plants) or large reflective surfaces (e.g., metal ducts, mirrors) to prevent false triggering.
Device Spacing: Maintain a minimum distance of 4 meters between multiple sensors to prevent mutual interference.
Mounting: Ensure the installation surface is vibration-free. Note that radar signals can penetrate surfaces; avoid moving objects directly behind the installation wall/ceiling.
Wiring Safety: Disconnect power before wiring. Use certified cables and ensure the circuit includes appropriate short-circuit and overload protection.
Disclaimer: Specifications are subject to change without notice. Please follow all wiring diagrams strictly. The manufacturer is not liable for issues caused by improper installation.
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
ETS (Engineering Tool Software)
ETS is the only official commissioning and programming software for the KNX wired smart home standard, used by professional engineers to configure wired systems in luxury homes and commercial buildings without relying on the cloud, ensuring ultimate stability and security.
FAQ
What is the core feature of this model in the KNX smart building bus system?
This is a standard KNX TP bus node device, and its core advantage is combining ranging and static presence detection. It supports up to 4 independent channels internally and has a powerful logic module output, enabling advanced lighting control logic like regional segmented detection and automatic day/night mode switching.
What are the requirements for the device's power supply wiring terminals?
The body provides two sets of terminals. Red/Black terminals connect to the KNX bus for communication; simultaneously, you must connect the Yellow/White auxiliary power terminals to provide external DC 12-30V low voltage to drive the radar microwave emission components (power consumption <3W).
How is the "programming button (PROG)" on the back of the body used during debugging?
Specifically used for KNX physical address assignment. Before issuing an address in the ETS software, press this programming button once, the indicator light in the multi-function window will light up, and the device enters the pending assignment state, ready to receive the bus address.
What is the role of adjusting the radar sensing surface to 60° in a complex lobby?
It can avoid obstacles in the middle of the ceiling (like giant chandeliers) by offset-installing the device in edge corners. By tilting the sensing surface 60° towards the target area, the detection beam can cover a 7.0m long by 3.0m wide walking and breathing detection zone, achieving flexible deployment.
How does the sensor combine with the built-in illuminance meter to achieve "fully automatic day/night mode"?
It internally integrates a 0 ~ 32,000 Lux high-precision illuminance meter (±4% accuracy). The KNX logic module can set two different light control thresholds based on illuminance values, allowing the system to trigger different light-on modes during the day when natural light is sufficient versus at night.
What size hole saw must be used for ceiling installation?
A hole saw with a diameter of 55 mm must be used, and the vertical clearance depth inside the ceiling must be greater than 65 mm to insert the device.
Will a thin metal ceiling on-site cause interference during installation?
Yes, it may even cause failure. Metal plates completely reflect 24G millimeter waves. You must ensure the sensing surface is completely exposed outside the metal ceiling, strictly prohibiting the detection cone cross-section from being blocked by metal structures.
During on-site maintenance, can the internal KNX configuration be directly overridden via a remote controller?
Supported. It not only supports modifying parameters via KNX telegrams, but the site also fully supports using the RC1 infrared remote controller aimed at the multi-function window to non-contactly override local parameters for instant debugging and verification.