The CTL-SEN-R5/2301 is a high-precision 24GHz millimeter-wave radar sensor designed for advanced occupancy detection. It features an adjustable range of 1.5 to 7m with centimeter-level accuracy and a flexible 0° to 60° tilt design for versatile installation. Beyond detecting movement, its "micro-motion" technology can identify static presence (like breathing), while customizable sensing zones and an integrated ambient light sensor enable intelligent automation for smart homes, offices, and healthcare, ensuring efficient energy management based on real-time human displacement.
Features
Supports motion, micro-motion, and stationary presence detection.
Features customizable multi-zone sensing (Segments A/B/C) and configurable proximity/recession distance thresholds.
Integrated high-precision sensor for accurate indoor illuminance monitoring.
Sensitivity and detection range can be configured independently.
Features a 0 to 60° adjustable detection angle for precise zone targeting.
Supports parameter configuration and query via IR remote control.
Indicator LED brightness automatically adjusts to ambient light levels.
Specifications
Communication Type
Dry Contact
Input Voltage
DC 12 to 30 V
Power Consumption
0.5 W (Max)
Dry Contact Output
Normally Open Mode, Normally Closed Mode, Normally Open Pulse, Normally Closed Pulse
Dry Contact Load
AC or DC ≤ 30 V, ≤ 200 mA
Indicator Light
LED
Detection Mode
24GHz FMCW Radar
Operating Frequency
24.00 to 24.25 GHz
Transmit Power
≤ 10 dBm
Installation Method
Recessed Ceiling Mount
Mounting Height
2.0 to 4.0 m
Detection Angle
360°
Detection Coverage
Mounting Height: 3 m At 0°: Φ 1.5 m detection range At 60°: 3.0 x 7.0 m detection range
Detection Range
1.5 to 7.0 m (sensor to target)
Illuminance Monitoring
0 to 32,000 Lux (Accuracy ±4%)
Delay Time
1 to 3,600 seconds
Product Size
Φ65 mm x 60 mm
Cutout Size
Φ55 mm
Product Weight
62 g
Cable Assembly
UL1007 20AWG Cable Length: 150 mm
Operating Temperature
Indoor -20 to 45°C
Operating Humidity
< 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Supporting flexible installation angle adjustments, this radar ranging sensor provides distinct coverage patterns at a standard mounting height of 3.0 meters:
0° vertical mounting: Delivers a circularly symmetrical coverage with a horizontal detection diameter of approximately 1.5 meters.
60° angled mounting: Delivers a directional fan-shaped/elliptical coverage, achieving a maximum forward detection span of up to 6.8 meters, a backward detection range of approximately 0.2 meters, a maximum overall transverse width of approximately 7.0 meters, and a longitudinal span of approximately 3.0 meters.
0° Front View
0° Front View
0° Top View
0° Top View
60° Front View
60° Front View
Dimensions
Product Dimensions
Applications
HomeHotelLightingOfficeSecurity
Mounting
Interference Avoidance: Avoid installing near constantly moving objects (e.g., curtains, plants) or large reflective surfaces (e.g., metal ducts, mirrors) to prevent false triggering.
Device Spacing: Maintain a minimum distance of 4 meters between multiple sensors to prevent mutual interference.
Mounting: Ensure the installation surface is vibration-free. Note that radar signals can penetrate surfaces; avoid moving objects directly behind the installation wall/ceiling.
Wiring Safety: Disconnect power before wiring. Use certified cables and ensure the circuit includes appropriate short-circuit and overload protection.
Disclaimer: Specifications are subject to change without notice. Please follow all wiring diagrams strictly. The manufacturer is not liable for issues caused by improper installation.
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
FAQ
What is the main positioning of this R5-Rang-REL dry contact model in low-voltage systems?
This is a pure low-voltage, networkless isolated model, providing pure dry contact signal output. It is used to connect to hotel guest room RCU hosts, alarms, or I/O acquisition modules, providing high-precision human occupancy signals with ranging and breathing detection capabilities.
What is the advantage of the "customizable multi-zone induction" feature in guest room applications?
By ranging, the sensor can distinguish displacement states like approaching/moving away. Combined with RCU host logic, different distance thresholds can be set (e.g., near the bed area or at the sink area) to trigger entirely different guest room lighting or curtain scenes.
Why does this model not have APP functions, and how should the output mode be configured on-site?
To guarantee extremely high local physical closed-loop reliability, interference-prone wireless modules were removed. Electricians directly use a screwdriver to rotate the decimal dials on the back of the body, which can combine to achieve fast blind adjustment of hardware-level NO/NC/Pulse output modes and sensitivity.
Can the internal dry contact be connected in series directly to control 220V luminaires?
Absolutely not. The dry contact can only withstand a maximum low-voltage signal of 30V/200mA. To control 220V loads, a high-power solid-state relay or AC contactor must be externally connected behind the dry contact.
What are the power supply specifications and rear wiring requirements for the sensor?
Adopts centrally supplied DC 12 ~ 30 V low-voltage input. The rear of the body uses a PH 2.0 mm 6-Pin socket, and the factory-matched cable is UL1007 20AWG, supporting quick plug-and-play wiring.
Is it feasible to install the body in a damp bathing environment?
Strongly not recommended. The housing protection rating is only IP20, lacking waterproof and moisture-proof capabilities. The operating environment humidity must be < 95% RH (non-condensing). It is strongly advised to avoid heavy moisture areas to prevent motherboard short circuits and corrosion.
What is the use of the 0° to 60° angle adjustment in access or aisle detection?
When the device can only be installed on the side ceiling, tilting the sensing surface 30° or 60° allows the radar ranging beam to strike diagonally in front of the door or the center of the aisle, eliminating the coverage blind spots caused by flat mounting.
Can parameters be fine-tuned via non-dial methods?
Supported. Besides coarse adjustments with mechanical dials, the site still fully supports using the RC1 infrared remote controller aimed at the multi-function window on the sensing surface to perform more detailed parameter overrides for delay time and sensitivity.