The CTL-SEN-R5/2108 is a high-precision human presence sensor powered by advanced 24GHz FMCW millimeter-wave radar technology. Featuring a versatile 0 to 60° adjustable detection angle, it allows for flexible positioning to target specific areas and minimize blind spots. By detecting micro-motions (such as breathing), the sensor accurately identifies both moving and stationary occupants. With a detection range of up to 8.0 meters and an integrated high-precision illuminance sensor (0 to 32,000 Lux), it is engineered to deliver optimal energy efficiency and automation for smart homes, commercial offices, and healthcare facilities.
Features
Supports motion, micro-motion, and stationary presence detection.
Integrated high-precision sensor for accurate indoor illuminance monitoring.
Supports multiple protocols via RS485, including Modbus-RTU and Active Reporting.
Features a 0 to 60° adjustable detection angle for precise zone targeting.
Sensitivity and detection range can be configured independently.
Supports parameter configuration and query via IR remote control.
Indicator LED brightness automatically adjusts to ambient light levels.
Specifications
Communication Type
RS485 + Dry Contact
Input Voltage
DC 12 to 30 V
Power Consumption
0.5 W (Max)
Serial Port Settings
Baud Rate: 1200 to 115200 Data Bits: 8 Parity: None, Even, Odd Stop Bits: 1 to 2 Default: 9600, 8, None, 1
Address Range
01 to 69 (Decimal)
Dry Contact Output
Normally Open Mode, Normally Closed Mode, Normally Open Pulse, Normally Closed Pulse
Dry Contact Load
AC or DC ≤ 30 V, ≤ 200mA
Indicator Light
LED
Detection Mode
24GHz FMCW Radar
Operating Frequency
24.00 to 24.25 GHz
Transmit Power
≤ 10 dBm
Installation Method
Recessed Ceiling Mount
Mounting Height
2.0 to 4.0 m
Detection Angle
360°
Detection Coverage
Mounting Height: 3 m At 0°: Φ 2.0 m detection range At 30°: 5.0 x 3.6 m detection range At 60°: 8.0 x 8.0 m detection range
Detection Range
1.5 to 8.0 m (sensor to target)
Sensitivity
0% to 100%
Illuminance Monitoring
0 to 32,000 Lux (Accuracy ±4%)
Delay Time
1 to 3,600 seconds
Product Size
Φ65 mm x 60 mm
Cutout Size
Φ55 mm
Product Weight
62 g
Cable Assembly
UL1007 20AWG Cable Length: 150 mm
Operating Environment
Indoor -20 to 45°C, Humidity < 95% RH (Non-condensing)
Storage Temperature
-40 to 85°C
Protection Level
IP20
Housing Material
PC
Range
Supporting flexible angle adjustments from 0° to 30° and 60°, this adjustable 24 GHz millimeter-wave radar breathing-presence sensor delivers tailored coverage patterns at a standard mounting height of 3.0 meters:
0° vertical mounting: Delivers a symmetrical circular coverage with a horizontal detection diameter of approximately 2.0 meters.
30° angled mounting: Delivers a directional fan-shaped coverage, achieving a maximum forward detection distance of up to 4.8 meters (with a backward range of approximately 0.2 meters), a maximum overall transverse span of approximately 5.0 meters, and a longitudinal span of approximately 3.6 meters.
60° angled mounting: Delivers a wide-range directional coverage, achieving a maximum forward detection distance of up to 8.0 meters, with both maximum transverse and longitudinal spans of approximately 8.0 meters.
0° Front View
0° Front View
0° Top View
0° Top View
30° Front View
30° Front View
Dimensions
Product Dimensions
Applications
HomeHotelLightingOfficeSecurity
Mounting
Interference Avoidance: Avoid installing near constantly moving objects (e.g., curtains, plants) or large reflective surfaces (e.g., metal ducts, mirrors) to prevent false triggering.
Device Spacing: Maintain a minimum distance of 4 meters between multiple sensors to prevent mutual interference.
Mounting: Ensure the installation surface is vibration-free. Note that radar signals can penetrate surfaces; avoid moving objects directly behind the installation wall/ceiling.
Wiring Safety: Disconnect power before wiring. Use certified cables and ensure the circuit includes appropriate short-circuit and overload protection.
Disclaimer: Specifications are subject to change without notice. Please follow all wiring diagrams strictly. The manufacturer is not liable for issues caused by improper installation.
Wiring Diagram
Wiring Diagram
Debugging
IR Remote Control
Designed for ultimate convenience and efficiency, this product supports quick on-site configuration and parameter reading using an infrared (IR) remote control. Once deployed, debugging and maintenance can be easily accomplished even without relying on a smart home platform.
Control4 - Composer Pro
Control4 Composer Pro is a professional-grade integration software for luxury whole-home audio/video and automation systems, exclusively available to certified dealers to seamlessly integrate entertainment hubs, complex subsystems, and custom smart scenes.
FAQ
What physical low-voltage interfaces does this R5-485 model support?
The body leads out a 6-core cable supporting an RS485 bus interface (Modbus-RTU protocol), and simultaneously provides 1-channel dry contact signal output (supporting Normally Open, Normally Closed, and Pulse modes).
What is the role of the R5's 0-60° angle adjustment function in low-voltage engineering?
Engineering sites are often limited by luminaire or duct positions, preventing centered sensor installation. The R5 can be offset-installed (e.g., in a corner) and then have its sensing surface tilted 30° or 60° towards the target area (e.g., a desk) for directional coverage, achieving flexible deployment.
What is the "decimal rotary dial" on the back of the body used to configure?
Specially designed for the 485 bus. Electricians can directly set the RS485 device address (supporting 01 ~ 99) on-site using a screwdriver on the dial, eliminating the tedious step of writing addresses with a computer.
What is the power supply specification for the system?
This is a pure low-voltage version, adopting a DC 12 ~ 30 V DC input power supply with a maximum power consumption not exceeding 0.5 W.
Can the internal dry contact directly control the 220V lighting circuit in the hallway?
Absolutely not. The dry contact can only withstand a maximum low-voltage signal of 30V/200mA, commonly used for sending alarms to third-party hosts. To control 220V high voltage, an external AC contactor must be connected.
How to avoid signal gibberish and interference when wiring multiple RS485 devices?
The 485 signal cable must use twisted shielded pair wire and be laid in separate conduits from high-voltage cables; the bus topology must be daisy-chained, with a 120-ohm terminating resistor in parallel at the end device. Additionally, radar spacing must be >4m to prevent microwave interference.
Will a large AC outdoor unit in the installation environment affect detection?
It will have a severe impact. The high-frequency vibration of the AC outdoor unit fan will be captured by the radar and misjudged as personnel walking. It is advised to adjust the angle of the R5 sensing surface away from the vibration source or lower the sensitivity.
Does it support local debugging using the RC1 remote controller?
Yes, supports locally issuing sensitivity, delay, and light-sensitive threshold configurations via the standard RC1 infrared remote controller aimed at the multi-function window of the sensing surface.