Model: CTL-USB-DALI This is a DALI-2 master controller and commissioning tool used for bus wiring verification, device addressing, grouping, and parameter configuration.
The CTL-USB-DALI is a DALI-2 master controller and commissioning tool used for bus wiring verification, device addressing, grouping, and parameter configuration. It connects to a PC via USB and operates with the dedicated DALI-Config software. Fully compliant with IEC 62386-103 (Part 103), it supports bidirectional bus communication for luminaire status tracking and sensor event binding, making it ideal for large-scale deployment and maintenance.
Features
Fully compatible with DALI-2 systems and IEC 62386-103 compliant controllers (sensors, panels, etc.). Supports configuration, commissioning, and localization.
Built-in 80 mA DALI power supply with auto-detection: turns on automatically if the bus lacks power, and shuts down if an external power supply is detected to ensure safety and isolation.
Supports "Add New Devices" (retains existing addresses and codes unaddressed ones) and "Re-address" (clears all addresses/groups for a full reassignment).
Supports software rewriting of core DALI parameters, including Max/Min Level, Power On/System Failure Level, Fade Time, and Fade Rate.
Specifications
Interface
USB 2.0
Protocol
IEC 62386-103
Compatibility
Windows 7 / Windows 10 / Windows 11 (32 bit、64 bit)
Software
DALI-Config
DALI Output Current
≤ 80 mA
Bus Power Control
Supports automatic On/Off switching
Dimensions
69 mm x 23.5 mm x 15.5 mm
Weight
13.2 g
Wiring Capacity
0.5 ~ 1.0 mm²
Included Cable
Retractable USB cable
Enclosure Material
PC、ABS
Dimensions
Product Dimensions
Applications
Home
Mounting
Never allow multiple independent power supplies on one physical bus. Verify bus power status before connection.
Always complete physical wiring and run the addressing program before configuring groups, scenes, or parameters.
Use 0.5 ~ 1.0 mm² conductor cross-section wires for DALI terminals and ensure secure connections.
After modifying parameters (like Max/Min Level or Power On Level), you must execute the "Save" command to permanently write the configuration to the device.
The "Locate" function forces max brightness or flashes the light for identification. Disable it immediately after use to avoid disrupting normal operations.
Always isolate upstream mains power before handling any physical wiring or DA+/DA- terminal changes.
Wiring Diagram
FAQ
What is the main use of CTL-USB-DALI?
This is a configuration and debugging tool for engineering maintenance personnel. By connecting a computer's USB interface and the DALI bus, and cooperating with DALI-Config software, it enables bus verification, device addressing, grouping, and scene parameter configuration for DALI lighting systems.
Does it support issuing parameters to sensors?
Supported. It is compatible with the DALI-2 protocol and supports digital configuration and event trigger binding for control devices (including sensors, panels) that comply with the IEC 62386-103 standard.
When debugging with this tool, is an external DALI power supply needed?
No. The device has a built-in DALI bus power supply with a maximum output capacity of 80mA, which is enough to drive some devices for physical addressing and testing during debugging.
If there is already a power supply on the project site bus, will plugging in this tool burn out the device?
The device has an automatic power detection mechanism. If it detects an independent power supply already on the bus, it will automatically turn off its internal power supply to avoid hardware damage caused by power conflicts.
What addressing modes does the software support?
Provides dual modes: "Add New Device" (retains the addresses of existing devices on the bus and only addresses new ones) and "Readdress" (clears all existing addresses of devices and performs a global unified readdressing).
After configuring the maximum brightness or power-off memory, why doesn't it take effect after unplugging the tool?
After modifying the operational logic parameters in the software, you must click the "Save" command for the configuration to be truly written into the internal memory of the terminal device (like a driver).
How does the "Physical Locate" function work?
After turning on the locate function, the corresponding driver power supply will force output at maximum brightness or make the indicator light flash, making it convenient for workers to identify which luminaire corresponds to which short address in a complex site. After identification, this function should be turned off promptly to restore normal operation.
What are the signal wire connection requirements for the DALI bus?
The cross-sectional area of the wires connected to the terminals must be strictly controlled between 0.5 ~ 1.0 mm^2 to ensure stable signal transmission of DA+ and DA-.